Validating Response of ac Micro-grid to Three Phase Short Circuit in Grid-Connected Mode Using Dynamic Analysis

Received: 1 April 2016     Accepted: 24 February 2017     Published: 11 March 2017
Views:       Downloads:
Abstract

This paper presents the results of attempt to validate the response dynamism of an 11kW, 575V wind turbine micro-grid connected to a 100MVA, 13.8kV utility under three phase bolted short circuit. The micro-grid was modeled using two Doubly-Fed Induction Generators (DFIGs). The test bed was developed in SimPowerSystems® at a system frequency of 50Hz with cut-in and cut-out wind speeds of 3ms-1 and 6ms-1, respectively. Short circuit fault is applied at 6.0s and withdrawn at 8.0s, and 50.0s dynamic response of the system is obtained for different fault locations, under voltage and reactive power controls of the wind turbine controller in grid-connected mode. The results of the study show bidirectional power flow due to power exchange between the utility and micro-grid, and poor post-fault sub-transient and transient instability associated with the micro-grid due to comparatively lower inertia. The study also shows that the micro-grid presents superior performance when stressed under Q control than under V control. Finally, the response of the test bed is found to be consistent with established short circuit theory, establishing its validity.

Published in International Journal of Electrical Components and Energy Conversion (Volume 2, Issue 4)
DOI 10.11648/j.ijecec.20160204.11
Page(s) 21-34
Creative Commons

This is an Open Access article, distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution and reproduction in any medium or format, provided the original work is properly cited.

Copyright

Copyright © The Author(s), 2017. Published by Science Publishing Group

Keywords

Micro-grid, Dynamic, DFIG, Micro-source, Fault

References
[1] Coffele, F., et al., Quantitative analysis of network protection blinding for systems incorporating distributed generation. IET Generation, Transmission & Distribution, 2012. 6 (12): p. 1218-1224.
[2] Adio, O. S., et al. Short circuit analysis for integration of 10MW Windfarm in Nigeria at the PCC. in 2013 IEEE Power and Energy Society General Meeting (PES). 2013.
[3] Rona, B. and Ö. Güler, Power system integration of wind farms and analysis of grid code requirements. Renewable and Sustainable Energy Reviews, 2015. 49: p. 100-107.
[4] Samaan, N., et al. Modeling of wind power plants for short circuit analysis in the transmission network. in 2008 IEEE Transmission and Distribution Conference and Exposition. 2008.
[5] Hatziargyriou, N., et al., Microgrids. IEEE Power and Energy Magazine, 2007. 5 (4): p. 78-94.
[6] Jan Machowski, Janusz W. Bialek, and J. R. Bumby, Power System Dynamics and Stability. 1997, England: John Wiley & Sons.
[7] Lasseter, R. H. MicroGrids. in 2002 IEEE Power Engineering Society Winter Meeting. 2002.
[8] Best, R. J., D. J. Morrow, and P. A. Crossley, Current transients in the small salient-pole alternator during sudden short-circuit and synchronisation events. IET Electric Power Applications, 2010. 4(9): p. 687-700.
[9] Chaudhary, M., S. M. Brahma, and S. J. Ranade. Validated short circuit modeling of Type 3 Wind Turbine Generator with crowbar protection. in North American Power Symposium (NAPS), 2013. 2013.
[10] Dos Santos, A. and M. T. C. d. Barros, Stochastic modeling of power system faults. Electric Power Systems Research, 2015. 126: p. 29-37.
[11] Haoen, L., A. Bose, and Z. Yang, On-line short-circuit current analysis and preventive control to extend equipment life. IET Generation, Transmission & Distribution, 2013. 7 (1): p. 69-75.
[12] Kersting, W. H. and G. Shirek. Short circuit analysis of IEEE test feeders. in 2012 IEEE PES Transmission and Distribution Conference and Exposition (T & D) 2012.
[13] Prajapati, J., V. Patel, and H. Patel. Load flow, short circuit and stability analysis using Matlab. in 2014 International Conference on Green Computing Communication and Electrical Engineering (ICGCCEE). 2014.
[14] Roennspiess, O. E. and A.E. Efthymiadis, A comparison of static and dynamic short circuit analysis procedures. IEEE Transactions on Industry Applications, 1990. 26(3): p. 463-475.
[15] Salon, S. J., et al. Short circuit analysis of large doubly-fed induction generators. in 2013 IEEE International Electric Machines & Drives Conference (IEMDC). 2013.
[16] Soni, N., S. Doolla, and M.C. Chandorkar, Improvement of Transient Response in Microgrids Using Virtual Inertia. IEEE Transactions on Power Delivery, 2013. 28(3): p. 1830-1838.
[17] Sulla, F., J. Svensson, and O. Samuelsson, Symmetrical and unsymmetrical short-circuit current of squirrel-cage and doubly-fed induction generators. Electric Power Systems Research, 2011. 81 (7): p. 1610-1618.
[18] Bracale, A., et al. Probabilistic short circuit analysis in electric power distribution systems including distributed generation. in 8th Mediterranean Conference on Power Generation, Transmission, Distribution and Energy Conversion (MEDPOWER 2012). 2012.
[19] Jen-Hao, T., Unsymmetrical Short-Circuit Fault Analysis for Weakly Meshed Distribution Systems. IEEE Transactions on Power Systems, 2010. 25(1): p. 96-105.
[20] Ouyang, J. and X. Xiong, Dynamic behavior of the excitation circuit of a doubly-fed induction generator under a symmetrical voltage drop. Renewable Energy, 2014. 71: p. 629-638.
[21] Aminu, M. A. and K. Solomon, A Review of Control Strategies for Microgrids. Advances in Research, 2016. 7 (3): p. 1-9.
[22] Aminu, M. A., Design of Reactive Power and Voltage Controllers for Converter-interfaced ac Microgrids. British Journal of Applied Science & Technology, 2016. 17 (1).
[23] Ferreira de Souza, W.a.S.-M., M. A. and Lopes, L. A. C., Power sharing control strategies for a three-phase microgrid in different operating condition with droop control and damping factor investigation. IET Renewable Power Generation, 2015. 9 (7): p. 831-839.
[24] Moghbel, M., et al. Reactive power control of DFIG wind power system connected to IEEE 14 bus distribution network. in Universities Power Engineering Conference (AUPEC), 2012 22nd Australasian. 2012.
[25] Mehdi, A., et al. Direct active and reactive power control of DFIG based wind energy conversion system. in 2014 International Symposium on Power Electronics, Electrical Drives, Automation and Motion (SPEEDAM). 2014.
[26] Pati, S. and S. Samantray. Decoupled control of active and reactive power in a DFIG based wind energy conversion system with conventional P-I controllers. in 2014 International Conference on Circuit, Power and Computing Technologies (ICCPCT). 2014.
[27] Olivares, D. E., et al., Trends in Microgrid Control. IEEE Transactions on Smart Grid, 2014. 5(4): p. 1905-1919.
[28] Soultanis, N. L. and N. D. Hatziargyriou. Control issues of inverters in the formation of LV microgrids. in 2007 IEEE Power Engineering Society General Meeting. 2007.
[29] Gopalan, S. A., V. Sreeram, and H. H. C. Iu, A review of coordination strategies and protection schemes for microgrids. Renewable and Sustainable Energy Reviews, 2014. 32: p. 222-228.
[30] Planas, E., et al., General aspects, hierarchical controls and droop methods in microgrids: A review. Renewable and Sustainable Energy Reviews, 2013. 17: p. 147-159.
[31] Romo, R. and O. Micheloud, Power quality of actual grids with plug-in electric vehicles in presence of renewables and microgrids. Renewable and Sustainable Energy Reviews, 2015. 46: p. 189-200.
[32] Soshinskaya, M., et al., Microgrids: Experiences, barriers and success factors. Renewable and Sustainable Energy Reviews, 2014. 40: p. 659-672.
[33] Zamora, R. and A.K. Srivastava, Controls for microgrids with storage: Review, challenges, and research needs. Renewable and Sustainable Energy Reviews, 2010. 14(7): p. 2009-2018.
[34] Vinothkumar, K. and M.P. Selvan. Enhanced fault ride-through scheme and coordinated reactive power control for DFIG. in 2010 IEEE International Conference on Sustainable Energy Technologies (ICSET). 2010.
Cite This Article
  • APA Style

    Maruf A. Aminu. (2017). Validating Response of ac Micro-grid to Three Phase Short Circuit in Grid-Connected Mode Using Dynamic Analysis. International Journal of Electrical Components and Energy Conversion, 2(4), 21-34. https://doi.org/10.11648/j.ijecec.20160204.11

    Copy | Download

    ACS Style

    Maruf A. Aminu. Validating Response of ac Micro-grid to Three Phase Short Circuit in Grid-Connected Mode Using Dynamic Analysis. Int. J. Electr. Compon. Energy Convers. 2017, 2(4), 21-34. doi: 10.11648/j.ijecec.20160204.11

    Copy | Download

    AMA Style

    Maruf A. Aminu. Validating Response of ac Micro-grid to Three Phase Short Circuit in Grid-Connected Mode Using Dynamic Analysis. Int J Electr Compon Energy Convers. 2017;2(4):21-34. doi: 10.11648/j.ijecec.20160204.11

    Copy | Download

  • @article{10.11648/j.ijecec.20160204.11,
      author = {Maruf A. Aminu},
      title = {Validating Response of ac Micro-grid to Three Phase Short Circuit in Grid-Connected Mode Using Dynamic Analysis},
      journal = {International Journal of Electrical Components and Energy Conversion},
      volume = {2},
      number = {4},
      pages = {21-34},
      doi = {10.11648/j.ijecec.20160204.11},
      url = {https://doi.org/10.11648/j.ijecec.20160204.11},
      eprint = {https://article.sciencepublishinggroup.com/pdf/10.11648.j.ijecec.20160204.11},
      abstract = {This paper presents the results of attempt to validate the response dynamism of an 11kW, 575V wind turbine micro-grid connected to a 100MVA, 13.8kV utility under three phase bolted short circuit. The micro-grid was modeled using two Doubly-Fed Induction Generators (DFIGs). The test bed was developed in SimPowerSystems® at a system frequency of 50Hz with cut-in and cut-out wind speeds of 3ms-1 and 6ms-1, respectively. Short circuit fault is applied at 6.0s and withdrawn at 8.0s, and 50.0s dynamic response of the system is obtained for different fault locations, under voltage and reactive power controls of the wind turbine controller in grid-connected mode. The results of the study show bidirectional power flow due to power exchange between the utility and micro-grid, and poor post-fault sub-transient and transient instability associated with the micro-grid due to comparatively lower inertia. The study also shows that the micro-grid presents superior performance when stressed under Q control than under V control. Finally, the response of the test bed is found to be consistent with established short circuit theory, establishing its validity.},
     year = {2017}
    }
    

    Copy | Download

  • TY  - JOUR
    T1  - Validating Response of ac Micro-grid to Three Phase Short Circuit in Grid-Connected Mode Using Dynamic Analysis
    AU  - Maruf A. Aminu
    Y1  - 2017/03/11
    PY  - 2017
    N1  - https://doi.org/10.11648/j.ijecec.20160204.11
    DO  - 10.11648/j.ijecec.20160204.11
    T2  - International Journal of Electrical Components and Energy Conversion
    JF  - International Journal of Electrical Components and Energy Conversion
    JO  - International Journal of Electrical Components and Energy Conversion
    SP  - 21
    EP  - 34
    PB  - Science Publishing Group
    SN  - 2469-8059
    UR  - https://doi.org/10.11648/j.ijecec.20160204.11
    AB  - This paper presents the results of attempt to validate the response dynamism of an 11kW, 575V wind turbine micro-grid connected to a 100MVA, 13.8kV utility under three phase bolted short circuit. The micro-grid was modeled using two Doubly-Fed Induction Generators (DFIGs). The test bed was developed in SimPowerSystems® at a system frequency of 50Hz with cut-in and cut-out wind speeds of 3ms-1 and 6ms-1, respectively. Short circuit fault is applied at 6.0s and withdrawn at 8.0s, and 50.0s dynamic response of the system is obtained for different fault locations, under voltage and reactive power controls of the wind turbine controller in grid-connected mode. The results of the study show bidirectional power flow due to power exchange between the utility and micro-grid, and poor post-fault sub-transient and transient instability associated with the micro-grid due to comparatively lower inertia. The study also shows that the micro-grid presents superior performance when stressed under Q control than under V control. Finally, the response of the test bed is found to be consistent with established short circuit theory, establishing its validity.
    VL  - 2
    IS  - 4
    ER  - 

    Copy | Download

Author Information
  • Department of Electrical and Computer Engineering, Curtin University, Sarawak, Malaysia

  • Sections